Abstract
"Void fractions were determined experimentally for Refrigerants 134a and 410A
condensing inside a smooth horizontal 7.04 mm (0.277"") i.d. tube. Tests that encompass a
range of mass fluxes from 75-450 kg/m2-s (55-330 klbm/ft2-hr) and inlet qualities of 0.13-
0.9 were performed at a temperature of 35°C (95 OF). The experimental apparatus and
procedures are described. The predictions of several existing correlations deviate from the
experimental data, which necessitates the formulation of a new void fraction correlation.
The correlation presented here is in terms of a Froude rate parameter, and accurately
predicts the experimental data."
Publisher
Air Conditioning and Refrigeration Center. College of Engineering. University of Illinois at Urbana-Champaign.
Series/Report Name or Number
Air Conditioning and Refrigeration Center TR-135
Type of Resource
text
Language
en
Permalink
http://hdl.handle.net/2142/11843
Sponsor(s)/Grant Number(s)
Air Conditioning and Refrigeration Center Project 74